Electric Mechanism CJ34

CJ34 operating mechanism can be used for closing and opening ZF10-126, ZF5T-126, ZF12-126, ZF4A-126, ZF31-126, ZF21-126, ZF29-126, ZF25-126, ZF39-126, ZF35-126, ZF34-252 as well as isolating switches, grounding switches and load switches of which the required torque is equivalent to that of the above switches.
Retail price
0.0
Market price
0.0
Number of views:
1003
Product serial number
Quantity
-
+
Stock:
Category
RETURN
1
Product description
Parameters

Summary

CJ34 operating mechanism can be used for closing and opening ZF10-126, ZF5T-126, ZF12-126, ZF4A-126, ZF31-126, ZF21-126, ZF29-126, ZF25-126, ZF39-126, ZF35-126, ZF34-252 as well as isolating switches, grounding switches and load switches of which the required torque is equivalent to that of the above switches.

The closing and opening positions as well as output angle of the mechanism are ensured by clutch and worm drive through a positive and negative rotation function of the motor. The mechanism has a manual function and an electric function at the same time.

Operating Conditions

1. Ambient air temperature: upper limit +40℃, lower limit -40℃

2. Altitude: no more than 3,000m

3. Air pressure: no more than 700Pa (equivalent to the air speed of 34m/s)

4. Monthly average humidity: no more than 90%

5. Air pollution degree: no more than IV grade stipulated in GB5582

6. Earthquake acceleration: no more than 0.4g in the horizontal direction; no more than 0.2g in the vertical direction

Main Technical Parameters

1. Output angle: 65±2° (customized according to user requirements)

2. Output torque: 128N m

3. Energy storage time under rated voltage: ≤6S

4. Technical parameters of energy storage motors

Model

HDZ-22403

Rated working voltage

220V

Rated output power of motor

240W

Normal working voltage range

85%--110%

5. CSK Magnetic Blow-out Switch

One-open & one-close (or two-open & two-close), the rated breaking current of a contact is 10A under AC220V, as well as 3A under DC220V.

6. Contactor

Model: 3TH4244E; producer: Siemens; power voltage: DC220V(AC220V); contact: four-open & four-close

7. Wiring Terminal

Current capable of passing continuously is 10A.

8. F10 Auxiliary Switch

The rated breaking current of the contact is 10A under AC220V, as well as 5A under DC220V.

9. Secondary Socket

24-pin, 46-pin, 56-pin and 64-pin secondary sockets are available.

Ordering Instructions

If you have other special requirements, please produce after negotiation with manufacturers.

We could not find any corresponding parameters, please add them to the properties table
Previous
Circuit Breaker Spring Mechanism CT252
Circuit Breaker Spring Mechanism CT252
Circuit Breaker Spring Mechanism CT126
Circuit Breaker Spring Mechanism CT126

Seek Survival By Quality, Seek Development By Quality, Seek Benefit From Quality

The company mainly produces high-voltage power transmission and transformation supporting equipment, intelligent complete switchgear, high-voltage GIS supporting products, etc., which are mainly used in high-voltage and UHV substation projects of the State Grid, Southern Power Grid, railway, communications, aviation, etc., all over the country.

Copyright © 2021 Tai’an Taihe Power Equipment Co., Ltd.        ICP Register No.:鲁ICP备16049525号      Webpage Copyright:WWW.300.NC JINAN2

Tai’an Taihe Power Equipment Co., Ltd.